Building System Guidelines
Building System Performance Guidelines
The Stanford Building System Performance Criteria Guide (BSPCG) is a set of guideline design documents to be used by faculty, staff, and design professionals during the planning and early design phases of a project. These reference documents illustrate the guidelines related to the variety of systems found on the Stanford campus. The Stanford BSPCG is to be used in conjunction with the Facilities Design Guidelines and applies to construction projects for all Stanford University facilities, including leased properties.
The Stanford BSPCG is not "all inclusive". It does not cover all of the facility systems found in the buildings nor does it cover all design criteria.
Central Vacuum Guidelines
|
Typical Lab |
1. Vacuum ( Hg) |
>24" |
2. Pumping Capacity @ 24" Hg |
Per Project Requirement |
3. Redundancy |
a. Yes |
4. Emergency Power |
No |
5. Alarms |
a. Yes |
Compressed Air Guidelines
ISO8573 Air Quality Standards |
Typical General Duty (Class 4) |
Typical Lab (Class 2) |
1. Oil (Parts per million by weight) |
<4 |
<0.08 |
2. Dew Points (°F) |
<38 |
<-40 |
3. Solid Particles (# particles per m3) |
<1000 |
<10 |
4. Design Air Pressure (psig) |
>100 |
>100 |
5. Flow Rate (CFM) |
a. Per Project Requirement |
a. Per Project Requirement |
6. Redundancy |
a. No |
a. No |
7. Emergency Power |
No |
Yes |
8. Alarms |
a. Yes |
a. Yes |
DDC Controls Guidelines
|
Typical Project |
1. Type of DDC System |
a. Yes |
2. Graphics Type |
a. Yes |
3. Graphics Display |
a. Yes b. Yes c. Yes d. Yes e. Yes f. Yes |
4. DDC Capability b. Communication bi-directionally with EM&CS using Modbus- |
a. Yes b. Yes |
5. Network connections |
a. Yes b. Yes |
6. Emergency Power |
a. Yes b. Yes |
Deionized Water Guidelines
Typical Lab | |
1. Flow rate (gpm) | Per Project Requirement |
2. Supply Pressure (psi) | Per Project Requirement |
3. Temperature ( °F) | Per Project Requirement |
4. Quality a. Resistivity (M-Ohm) @ 25°C b. Total Oxidizable Carbon (ppb) c. Particles ( cts/L) d. Oxygen (ppb) e. Bacteria (cfu/vol) f. Silica (ppb) g. Metals & other elements (ppt) |
a. 4-18 b. Per Project Requirement c. Per Project Requirement d. Per Project Requirement e. Per Project Requirement f. Per Project Requirement g. Per Project Requirement |
5. Redundancy a. Storage Tank b. Pumps |
a. Yes b. Yes |
6. Emergency Power | No |
7. Alarms a. Pressure b. Resistivity c. Particles d. TOC e. Silica f. Tank High & Low Alarm |
a. Yes b. Yes c. No d. No e. No f. Yes |
Environmental Guidelines
Typical Lab | Critical Lab | |
1. Temperature ( °F) | 70°F +/- 3°F | 70°F +/-1.8°F |
2. Relative Humidity (%) | None | 45%+/-5% |
3. Noise Level rating | RC 45 | RC 35 |
4. Vibration (micro inches per second) | None | <125 |
5. Illuminance Level (fc) | 70 to 100 | 70 to 100 |
6. Clean room (ISO/Class) | None | ISO 5/ C100 |
7. Alarms a. Temperature b. Relative Humidity c. Clean Room |
a. Yes b. None c. None |
a. Yes b. Yes c. Yes |
Process Cooling Water Guidelines
Typical Lab | |
1. System Design a. Open Tank b. Closed Loop |
a. Yes b. No |
2. Flow rate (gpm) | Per Project Requirement |
3. Maximum Supply Pressure (psi) | Per Project Requirement |
4. Differential Pressure (psi) | Per Project Requirement |
5. Temperature ( °F) | 60 - 65 |
6. Quality a. Particles (µm) b. pH value c. Electrical conductivity (µS/cm) d. Other |
a. <50 b. Per Project Requirement c. Per Project Requirement d. Per Project Requirement |
7. Redundancy a. City Water back up b. Pumps |
a. Yes b. Yes |
8. Emergency Power | No |
9. Alarms a. Pressure b. Temperature c. Pump Failure |
a. Yes b. Yes c. Yes |